Isolated protective cabin

The positive pressure protective cabin is an air purification and isolation device that not only sends clean air into the room to make the indoor air clean, but also generates positive pressure to keep the room in a positive pressure state relative to the outside. It can discharge, disinfect and purify the air with bacteria, which is a safe purification equipment. The equipment has ultraviolet disinfection and ozone disinfection capabilities, which can effectively ensure the safety of the indoor environment.

Description

 Equipment Features
The positive pressure protective cabin is an air purification and isolation device that not only sends clean air into the room to make the indoor air clean, but also generates positive pressure to keep the room in a positive pressure state relative to the outside. It can discharge, disinfect and purify the air with bacteria, which is a safe purification equipment.
The equipment has ultraviolet disinfection and ozone disinfection capabilities, which can effectively ensure the safety of the indoor environment.
 
 Use environment and conditions:
temperature

5℃~40℃

Relative humidity

≤85%

Atmospheric pressure

86kPa~106kPa

power supply

AC220V,50Hz

 

product features:

According to the type of protection against electric shock: Class I
Classification by degree of protection against electric shock: Type B applied part
The power type of this product: AC220V
Classified according to the degree of protection against ingress: IPX0
It is prohibited to use in the case of a mixture of flammable anesthetic gas and air or a mixture of oxygen or nitrous oxide.
Equipment operation mode: intermittent loading and continuous operation
 
technical parameter
Parameter / model positive pressure cabin
 cabin pressure

10~20Pa

cabin cleanliness ISO Class 8 (The number of particles ≧0.5um does not exceed 3,520,000 particles/m3)
Exhaust Air Particle Concentration ISO 6 grade (the number of particles ≧0.3um does not exceed 102,000 particles/m3)
Terminal ozone disinfection concentration

≥20PPM

Terminal ozone disinfection time

30min

noise

≤68 dB

Indoor illumination

≥300 Lux

power supply

220V 50Hz 

Power consumption

500W

 